A plain-language summary of this CVE is being written; the description below is the NVD's own text.
Description
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Affected products
From the NVD's configuration data (CPE), vendor first.
- Hitachienergy rtu500 firmware, rtu500
Weakness type
References
- publisher.hitachienergy.com /preview
- search.abb.com /library/Download.aspx
Ingati scans your site every week and tells you when a CVE like this one affects something it found there.